时间:2022-09-22 预(yu)览(lan):874
电(dian)缆故障(zhang)查找可(ke)以(yi)使(shi)用(yong)小(xiao)电流或者(zhe)小(xiao)电容(rong),不建(jian)议使用(yong)限(xian)流电(dian)阻。如果(guo)使(shi)用ZS系列(lie)的电缆故障查(cha)找(zhao),应(ying)在高(gao)压(ya)回路(lu)内(nei)与(yu)限(xian)流电(dian)阻(zu)进(jin)行(xing)串(chuan)接,击穿电(dian)缆(lan)故(gu)障点(dian)或(huo)者(zhe)闪(shan)烁时,能(neng)起限(xian)止电(dian)流(liu)作(zuo)用(yong),避(bi)免损(sun)坏(huai)设备。关于电缆(lan)故障查找(zhao)的(de)判断方法有以下(xia)几种(zhong):
1、被测电(dian)缆(lan)一芯或(huo)几(ji)芯(xin)对地(di)存(cun)在绝缘电(dian)阻,或者绝(jue)缘(yuan)电(dian)阻小(xiao)于(yu)100Ω时,可(ke)判(pan)断(duan)为低(di)电阻接(jie)地(di)或(huo)者(zhe)短路(lu)缺点(dian)。
2、被(bei)测电(dian)缆(lan)一(yi)芯(xin)或几芯(xin)对地存在绝缘(yuan)电(dian)阻,或(huo)者绝(jue)缘电阻与(yu)正常值(zhi)相差(cha)很大(da),且大于100Ω,可判断(duan)为(wei)高(gao)电(dian)阻(zu)接地缺(que)点。该现(xian)象表(biao)现(xian)为闪(shan)络延(yan)续(xu)多(duo)次(ci)存在(zai),距(ju)离(li)之间(jian)几秒(miao)或(huo)者几分(fen)钟(zhong)。
3、被(bei)测电(dian)缆(lan)的电芯(xin)对(dui)地绝(jue)缘(yuan)电阻值(zhi)较高或(huo)者(zhe)正常(chang)值(zhi),要停止进(jin)行(xing)导体延续(xu)性试验(yan),检查(cha)是(shi)否(fou)有(you)断(duan)线(xian),如果有(you)即可判断为(wei)断(duan)线(xian)缺(que)点(dian)。
4、闪络性(xing)缺(que)点(dian)常见(jian)于电缆预(yu)防耐(nai)压性(xing)实(shi)验,部位常见(jian)在(zai)电(dian)缆(lan)的(de)终(zhong)端以及(ji)中直接头(tou)。进行(xing)电缆(lan)故障查找(zhao)可(ke)以使(shi)用兆(zhao)欧(ou)表测量各相的绝(jue)缘电阻(zu)。